Gas Orifice Size Chart and Calculator

A gas orifice is the small brass fitting with a precisely drilled hole that meters gas into a burner. The size of that hole and the gas pressure behind it set the burner's input in BTU per hour, which is why natural gas and propane (LP) appliances use different orifices. The charts below give the approximate input for every number drill size from #1 to #80 and for common metric sizes, and the orifice calculator on this page runs the same math for any pressure, heating value or altitude.

Use these numbers as a reference, not as a conversion recipe. Your appliance's rating plate and the maker's conversion kit are the authority, and orifice changes and gas conversions are work for a licensed gas installer. See Safety below.

How to Read the Orifice Size Chart

  • Find the size stamped on the orifice. Most burner orifices are stamped with a number drill size, such as #34 (Kozy Heat writes it "#34 (DMS)"). Some makers stamp a metric size in millimeters instead; Empire, for example, uses orifices marked 1.45, 2.25 and 2.40. The higher the drill number, the smaller the hole: a #80 is 0.0135 in. and a #1 is 0.228 in.
  • Read across to your gas and pressure. Each figure is the BTU per hour through one orifice at sea level, at the manifold pressure in the column heading. Manifold pressure is measured at the gas valve's outlet pressure tap with a manometer, and the right value is on the rating plate or in the manual.
  • Add up every orifice on the burner. A burner with front and rear orifices fires at their total. Example: an Empire DVCT36CBP9 converted to natural gas uses a #48 front orifice and a 2.40 mm rear orifice. The chart gives 16,400 + 25,300 = 41,700 BTU/hr, and Empire rates it at 40,000 BTU/hr.
  • Pressure matters less than you might think. Flow rises with the square root of pressure, so raising a natural gas manifold from 3.5 to 4.0 in. w.c. adds only about 7%.
  • Treat every figure as plus or minus 5%. Real orifices vary with the shape of the hole and the burner design. Against seven maker-rated fireplace inputs, these charts land within about 4%.
  • Pilot orifices are a different animal. Pilot injectors are tiny and are often marked with the maker's own code rather than a drill number (Kozy Heat marks one natural gas pilot injector "#.023NG", a decimal size). Replace a pilot injector by part number, not from this chart.

Natural Gas Orifice Size Chart (3.5 in. w.c.)

Natural gas at 3.5 in. w.c. manifold pressure, a common setting for gas fireplaces, inserts and stoves (Empire's conversion instructions, for example, set natural gas to about 3.5 in. w.c. at the valve outlet). Basis: 1,000 BTU per cubic foot, specific gravity 0.60, discharge coefficient 0.90, sea level. Values under 10,000 are rounded to the nearest 10 BTU/hr, larger values to the nearest 100.

Drill size Diameter (in.) Diameter (mm) Natural gas BTU/hr at 3.5 in. w.c.
#1 0.228 5.79 147,200
#2 0.221 5.61 138,300
#3 0.213 5.41 128,500
#4 0.209 5.31 123,700
#5 0.2055 5.22 119,600
#6 0.204 5.18 117,800
#7 0.201 5.11 114,400
#8 0.199 5.05 112,100
#9 0.196 4.98 108,800
#10 0.1935 4.91 106,000
#11 0.191 4.85 103,300
#12 0.189 4.80 101,100
#13 0.185 4.70 96,900
#14 0.182 4.62 93,800
#15 0.180 4.57 91,700
#16 0.177 4.50 88,700
#17 0.173 4.39 84,700
#18 0.1695 4.31 81,300
#19 0.166 4.22 78,000
#20 0.161 4.09 73,400
#21 0.159 4.04 71,600
#22 0.157 3.99 69,800
#23 0.154 3.91 67,200
#24 0.152 3.86 65,400
#25 0.1495 3.80 63,300
#26 0.147 3.73 61,200
#27 0.144 3.66 58,700
#28 0.1405 3.57 55,900
#29 0.136 3.45 52,400
#30 0.1285 3.26 46,800
#31 0.120 3.05 40,800
#32 0.116 2.95 38,100
#33 0.113 2.87 36,200
#34 0.111 2.82 34,900
#35 0.110 2.79 34,300
#36 0.1065 2.71 32,100
#37 0.104 2.64 30,600
#38 0.1015 2.58 29,200
#39 0.0995 2.53 28,000
#40 0.098 2.49 27,200
#41 0.096 2.44 26,100
#42 0.0935 2.37 24,800
#43 0.089 2.26 22,400
#44 0.086 2.18 20,900
#45 0.082 2.08 19,000
#46 0.081 2.06 18,600
#47 0.0785 1.99 17,400
#48 0.076 1.93 16,400
#49 0.073 1.85 15,100
#50 0.070 1.78 13,900
#51 0.067 1.70 12,700
#52 0.0635 1.61 11,400
#53 0.0595 1.51 10,000
#54 0.055 1.40 8,570
#55 0.052 1.32 7,660
#56 0.0465 1.18 6,120
#57 0.043 1.09 5,240
#58 0.042 1.07 4,990
#59 0.041 1.04 4,760
#60 0.040 1.02 4,530
#61 0.039 0.99 4,310
#62 0.038 0.97 4,090
#63 0.037 0.94 3,880
#64 0.036 0.91 3,670
#65 0.035 0.89 3,470
#66 0.033 0.84 3,080
#67 0.032 0.81 2,900
#68 0.031 0.79 2,720
#69 0.0292 0.74 2,410
#70 0.028 0.71 2,220
#71 0.026 0.66 1,910
#72 0.025 0.64 1,770
#73 0.024 0.61 1,630
#74 0.0225 0.57 1,430
#75 0.021 0.53 1,250
#76 0.020 0.51 1,130
#77 0.018 0.46 920
#78 0.016 0.41 720
#79 0.0145 0.37 600
#80 0.0135 0.34 520

Propane (LP) Orifice Size Chart (10 and 11 in. w.c.)

Propane at two manifold pressures. Many gas fireplaces, inserts and stoves set propane to about 10.0 in. w.c. at the valve outlet (Empire's propane conversion instructions are one example), while the National Fuel Gas Code's propane orifice table is based on 11.0 in. w.c. Use the column that matches your rating plate or manual. Basis: 2,500 BTU per cubic foot, specific gravity 1.52, discharge coefficient 0.90, sea level.

Drill size Diameter (in.) Diameter (mm) Propane BTU/hr at 10.0 in. w.c. Propane BTU/hr at 11.0 in. w.c.
#1 0.228 5.79 390,800 409,900
#2 0.221 5.61 367,200 385,100
#3 0.213 5.41 341,100 357,700
#4 0.209 5.31 328,400 344,400
#5 0.2055 5.22 317,500 333,000
#6 0.204 5.18 312,800 328,100
#7 0.201 5.11 303,700 318,500
#8 0.199 5.05 297,700 312,200
#9 0.196 4.98 288,800 302,900
#10 0.1935 4.91 281,500 295,200
#11 0.191 4.85 274,200 287,600
#12 0.189 4.80 268,500 281,600
#13 0.185 4.70 257,300 269,800
#14 0.182 4.62 249,000 261,200
#15 0.180 4.57 243,600 255,500
#16 0.177 4.50 235,500 247,000
#17 0.173 4.39 225,000 236,000
#18 0.1695 4.31 216,000 226,500
#19 0.166 4.22 207,100 217,300
#20 0.161 4.09 194,900 204,400
#21 0.159 4.04 190,000 199,300
#22 0.157 3.99 185,300 194,300
#23 0.154 3.91 178,300 187,000
#24 0.152 3.86 173,700 182,200
#25 0.1495 3.80 168,000 176,200
#26 0.147 3.73 162,400 170,400
#27 0.144 3.66 155,900 163,500
#28 0.1405 3.57 148,400 155,600
#29 0.136 3.45 139,000 145,800
#30 0.1285 3.26 124,100 130,200
#31 0.120 3.05 108,300 113,500
#32 0.116 2.95 101,200 106,100
#33 0.113 2.87 96,000 100,700
#34 0.111 2.82 92,600 97,100
#35 0.110 2.79 91,000 95,400
#36 0.1065 2.71 85,300 89,400
#37 0.104 2.64 81,300 85,300
#38 0.1015 2.58 77,400 81,200
#39 0.0995 2.53 74,400 78,100
#40 0.098 2.49 72,200 75,700
#41 0.096 2.44 69,300 72,700
#42 0.0935 2.37 65,700 68,900
#43 0.089 2.26 59,500 62,500
#44 0.086 2.18 55,600 58,300
#45 0.082 2.08 50,500 53,000
#46 0.081 2.06 49,300 51,700
#47 0.0785 1.99 46,300 48,600
#48 0.076 1.93 43,400 45,500
#49 0.073 1.85 40,100 42,000
#50 0.070 1.78 36,800 38,600
#51 0.067 1.70 33,700 35,400
#52 0.0635 1.61 30,300 31,800
#53 0.0595 1.51 26,600 27,900
#54 0.055 1.40 22,700 23,800
#55 0.052 1.32 20,300 21,300
#56 0.0465 1.18 16,300 17,000
#57 0.043 1.09 13,900 14,600
#58 0.042 1.07 13,300 13,900
#59 0.041 1.04 12,600 13,300
#60 0.040 1.02 12,000 12,600
#61 0.039 0.99 11,400 12,000
#62 0.038 0.97 10,900 11,400
#63 0.037 0.94 10,300 10,800
#64 0.036 0.91 9,740 10,200
#65 0.035 0.89 9,210 9,660
#66 0.033 0.84 8,190 8,590
#67 0.032 0.81 7,700 8,070
#68 0.031 0.79 7,220 7,580
#69 0.0292 0.74 6,410 6,720
#70 0.028 0.71 5,890 6,180
#71 0.026 0.66 5,080 5,330
#72 0.025 0.64 4,700 4,930
#73 0.024 0.61 4,330 4,540
#74 0.0225 0.57 3,810 3,990
#75 0.021 0.53 3,320 3,480
#76 0.020 0.51 3,010 3,150
#77 0.018 0.46 2,440 2,550
#78 0.016 0.41 1,920 2,020
#79 0.0145 0.37 1,580 1,660
#80 0.0135 0.34 1,370 1,440

Metric Orifice Size Chart (mm)

Many fireplace and grill orifices are sized in millimeters, such as Empire's 1.45 mm and 1.55 mm fireplace orifices or Broilmaster's 1.05 to 2.37 mm grill orifices. Same basis as the tables above.

Orifice (mm) Diameter (in.) Natural gas BTU/hr at 3.5 in. w.c. Propane BTU/hr at 10.0 in. w.c. Propane BTU/hr at 11.0 in. w.c.
0.80 0.0315 2,810 7,460 7,820
0.85 0.0335 3,170 8,420 8,830
0.90 0.0354 3,550 9,440 9,900
0.95 0.0374 3,960 10,500 11,000
1.00 0.0394 4,390 11,700 12,200
1.05 0.0413 4,840 12,800 13,500
1.10 0.0433 5,310 14,100 14,800
1.15 0.0453 5,800 15,400 16,200
1.20 0.0472 6,320 16,800 17,600
1.25 0.0492 6,860 18,200 19,100
1.30 0.0512 7,420 19,700 20,700
1.35 0.0531 8,000 21,200 22,300
1.40 0.0551 8,600 22,800 24,000
1.45 0.0571 9,230 24,500 25,700
1.50 0.0591 9,870 26,200 27,500
1.55 0.0610 10,500 28,000 29,400
1.60 0.0630 11,200 29,800 31,300
1.65 0.0650 11,900 31,700 33,300
1.70 0.0669 12,700 33,700 35,300
1.75 0.0689 13,400 35,700 37,400
1.80 0.0709 14,200 37,800 39,600
1.85 0.0728 15,000 39,900 41,800
1.90 0.0748 15,800 42,100 44,100
1.95 0.0768 16,700 44,300 46,500
2.00 0.0787 17,600 46,600 48,900
2.05 0.0807 18,400 49,000 51,400
2.10 0.0827 19,400 51,400 53,900
2.15 0.0846 20,300 53,900 56,500
2.20 0.0866 21,200 56,400 59,100
2.25 0.0886 22,200 59,000 61,900
2.30 0.0906 23,200 61,600 64,600
2.35 0.0925 24,200 64,300 67,500
2.40 0.0945 25,300 67,100 70,400
2.45 0.0965 26,300 69,900 73,400
2.50 0.0984 27,400 72,800 76,400
2.55 0.1004 28,500 75,800 79,500
2.60 0.1024 29,700 78,800 82,600
2.65 0.1043 30,800 81,800 85,800
2.70 0.1063 32,000 84,900 89,100
2.75 0.1083 33,200 88,100 92,400
2.80 0.1102 34,400 91,400 95,800
2.85 0.1122 35,600 94,600 99,300
2.90 0.1142 36,900 98,000 102,800
2.95 0.1161 38,200 101,400 106,400
3.00 0.1181 39,500 104,900 110,000
3.05 0.1201 40,800 108,400 113,700
3.10 0.1220 42,200 112,000 117,400
3.15 0.1240 43,500 115,600 121,300
3.20 0.1260 44,900 119,300 125,100
3.25 0.1280 46,400 123,100 129,100
3.30 0.1299 47,800 126,900 133,100
3.35 0.1319 49,300 130,800 137,100
3.40 0.1339 50,700 134,700 141,300
3.45 0.1358 52,200 138,700 145,500
3.50 0.1378 53,800 142,700 149,700

Heating Values Used: 1,000 vs 2,500 BTU per Cubic Foot

The charts assume 1,000 BTU per cubic foot for natural gas and 2,500 for propane, the round numbers most charts and appliance manuals work from. Real gas varies a little:

  • Natural gas: gas delivered in the US averaged about 1,037 BTU per cubic foot in 2025, according to the US Energy Information Administration, so real input on typical pipeline gas can run up to about 4% above these figures. Your gas utility can tell you the heating value at your address.
  • Propane: propane vapor carries roughly 2,500 BTU per cubic foot at 60 °F. RegO's LP-gas manual lists 2,488 for commercial propane and the NFPA 58 property table lists 2,516, so the 2,500 basis here is within about 1% of both.
  • Why propane orifices are so much smaller: propane carries 2.5 times the energy per cubic foot and runs at about three times the pressure. For the same input, a propane orifice at 10 in. w.c. needs only about 38% of the hole area of a natural gas orifice at 3.5 in. w.c., or roughly 0.6 times the diameter. A 30,000 BTU/hr burner works out to a #37 or #38 orifice on natural gas and a #52 or #53 on propane.
  • Why the wrong orifice is dangerous: a natural gas orifice run on propane at 10 in. w.c. would pass about 2.7 times the heat it was sized for, and a propane orifice on natural gas only about 38%.

To check what an appliance is really burning, the installer can clock the gas meter with every other gas appliance off: 3,600 divided by the seconds it takes to use one cubic foot gives cubic feet per hour, and that times the heating value gives BTU per hour.

High-Altitude Orifice Sizing and Derating

These charts are for sea level. In the US, gas appliances installed above 2,000 ft are derated: input is reduced 4% for each 1,000 ft above sea level, following the American Gas Association guideline that appliance manuals cite. In Canada, the standard rating covers 0 to 4,500 ft, and above 4,500 ft the certified high-altitude rating is reduced 4% for each additional 1,000 ft (CSA B149.1).

  • Example: a fireplace rated 30,000 BTU/hr at sea level, installed at 5,000 ft, should run at about 30,000 × (1 − 5 × 0.04) = 24,000 BTU/hr.
  • The derate is done with a smaller orifice. Makers supply high-altitude orifices; Lennox's changeover and high-altitude kits for its UHCM unit heaters, for example, step from a #41 orifice up to 4,000 ft to a #44 at 4,001 to 8,000 ft and a #47 at 8,001 to 10,000 ft. Keep the manifold pressure at the rating plate value.
  • Check the gas, too. Some utilities at high elevation deliver gas with a lower heating value, which lowers input on its own. Carrier's furnace instructions, for example, size orifices from the heating value the local utility reports at the installed altitude. Ask your utility, then follow the appliance maker's high-altitude instructions.

When you enter an altitude above 2,000 ft, the calculator applies the 4% rule to your target input and sizes the orifice from sea-level values. That simple method leans toward a smaller orifice; the maker's high-altitude orifice size always overrides it.

Safety: Who Should Change a Gas Orifice

Orifice changes and gas conversions are work for a licensed gas installer or the dealer's service technician, not a homeowner project. The makers' conversion instructions say so: Empire's kits are to be installed by an Empire distributor or other qualified agency, and Kozy Heat warns that if its instructions are not followed exactly, a fire, explosion or carbon monoxide may result, causing property damage, personal injury or loss of life.

  • Convert only with the maker's kit for your exact model. A conversion is more than an orifice. Empire's fireplace kits include front and rear burner orifices, a SIT valve conversion kit and a conversion label, and the steps include resetting the air shutters; Kozy Heat's kits include burner orifices, a pilot injector, a stepper motor and labels. Find your model number first, or check the rating plate.
  • Do not drill, ream or substitute an orifice from a chart to change an appliance's input. Use the size the maker specifies for your model, gas and altitude.
  • After the work, the installer should: check every connection for leaks with soapy water, set inlet and manifold pressure with a manometer to the rating plate, verify the input (clock the meter, or check manifold pressure where there is no meter), check the main burner and pilot flames, run the safety shutdown test (on Empire's IPI fireplaces, pilot gas flow should stop within 30 seconds of turning the unit off) and fix the gas conversion label to the appliance.
  • If you smell gas, do not try to light any appliance. Leave the building and call your gas supplier or 911 from outside. More in our gas fireplace safety tips.

Orifices and Conversion Kits We Carry

Match the part number in your manual or on your model's parts list before ordering. A kit or orifice made for one model is not a universal part, even when the stamped size matches.

What you are doing What it takes Part to check Parts we carry
Converting a fireplace, insert or stove from natural gas to propane, or back The maker's conversion kit for your exact model: burner orifices, pilot injector or pilot orifice, valve conversion parts and a conversion label Conversion kit by model number (find it in the manual or on the rating plate) Empire 31054, NG to LP (DVP20MS, DVP20CC)
Empire 32877, LP to NG (DVCP36BP, DVCC36BP)
Empire BVCK36P, NG to LP (BVD34FP, BVD36FP)
Empire 40513, LP to NG (DVLL36BP)
Majestic LPK-ECHEL48 (LP)
Superior GCKSLLXNP, NG to LP
Superior GCKSIT3035MNP, NG to LP (millivolt)
HHT 40LCKN (NG)
Heatilator and Heat N Glo LPK-4836 (LP)
Astria Scorpio and Superior F2183 (LP)
All gas valves and conversion kits
Replacing a damaged, cross-threaded or lost main burner orifice (same gas) A genuine orifice with the same stamped size and thread as the original Burner orifice by part number (front and rear orifices are often different sizes) Empire P208, 1.45 mm
Empire P258, 1.55 mm
Empire P185, #52
Empire P182, #55
Empire P243, #36 (VFLB48FP)
Empire P193, #64
Buck PO 44MVORF, NG rear
Buck PO 54MVORF, LP rear
All Empire parts
Pilot injector damaged, or the pilot needs the other gas Pilot orifice (injector) for the gas type; pilot injectors are marked with the maker's own codes Pilot orifice by part number SIT 0.977.166 pilot orifice, NG
SIT 0.977.167 pilot orifice, LP
HHT 446-517 pilot orifice, LP
All HHT parts
Converting a gas grill The grill maker's conversion kit, or the matching orifices Grill conversion kit or burner orifice Broilmaster BCK1000, LP to NG (P3, P4, D3, D4)
Broilmaster BCK1001, NG to LP (P3, P4, D3, D4)
Broilmaster B056647, NG orifice (P and D series)
Broilmaster BR0047, 1.30 mm orifice
MHP GGNAT-KIT, LP to NG (WNK, TJK)
MHP GGLP-KIT, NG to LP (WNK, TJK)
All Broilmaster parts
Converting a furnace The furnace maker's LP or natural gas kit for that model Furnace conversion kit Lennox 25W20, NG to LP
Lennox 44W49, LP to NG
Carrier KGAPN3901ALL, LP to NG
Rheem FP-02 (LP)

Find parts for your exact appliance: gas valves and conversion kits · Empire fireplace parts · HHT (Heat N Glo, Heatilator, Quadra-Fire) parts · Broilmaster grill parts.

Gas Orifice FAQ

What size orifice do I need for my BTU rating?

Divide the rated input by the number of orifices, then find the drill size closest to that figure without going over, in the column for your gas and pressure. For 30,000 BTU/hr on one orifice, that is a #38 (about 29,200 BTU/hr) on natural gas at 3.5 in. w.c., or a #53 (about 26,600) to #52 (about 30,300) on propane at 10 in. w.c. On a fireplace, the orifice the maker lists for your model always wins.

What is the difference between a natural gas and a propane orifice?

The hole size. For the same input, a propane orifice is roughly 0.6 times the diameter of the natural gas one, because propane carries more energy per cubic foot and runs at higher pressure. The fittings can look alike, so read the stamped size.

Can I convert my gas fireplace by changing the orifice?

No. A conversion also changes the valve's regulated pressure (about 3.5 in. w.c. on natural gas vs 10.0 on propane for Empire's fireplaces, done with a SIT valve conversion kit), often the pilot injector, and sometimes the air shutter setting. Use the maker's kit for your model and have a qualified installer do the work.

How do I adjust orifice size for high altitude?

In the US, reduce the sea-level input 4% for every 1,000 ft above sea level once you are above 2,000 ft, and use the smaller orifice the maker specifies for that elevation. At 6,000 ft that is a 24% reduction. Also ask your utility for the heating value of your gas, because lower-BTU gas at altitude already reduces input.

Are orifice sizes the same as drill sizes?

Usually. Most orifices are stamped with a number drill size (#1 to #80) or a metric diameter in millimeters, and the hole matches that drill. The drill diameters in these charts follow the ASME B94.11M twist drill standard. Pilot injectors are the exception; many carry the maker's own code.

How These Numbers Were Calculated

Every value comes from the standard orifice flow equation: Q = 1658.5 × Cd × A × √(P ÷ G), where Q is cubic feet per hour, A is the hole area in square inches (π × d² ÷ 4), P is the manifold pressure in inches of water column, G is the gas specific gravity (air = 1) and Cd is the discharge coefficient. BTU per hour = Q × heating value. We used Cd 0.90 and specific gravity 0.60 for natural gas, values that reproduce the National Fuel Gas Code (NFPA 54) natural gas orifice table, and specific gravity 1.52 for propane.

We checked the results three ways. Against the NFPA 54 natural gas values at 3.5 in. w.c., 62 of 63 drill sizes agree within 5% and 56 within 1%; the one miss is a misprinted row in the reprint we used. Against the NFPA 54 propane table at 11 in. w.c., reprinted in RegO's LP-Gas Serviceman's Manual, our propane values run 2% to 3% lower on the same heating value, on every row but one misprinted one. Against seven maker-rated fireplace inputs from Empire and Kozy Heat conversion instructions, the computed input lands within about 4% of the rating every time (the widest gap is 4.1%, Empire's DVCT36 on natural gas).

Gas orifice size calculator

Find the drill size for a BTU rating, or the BTU rating of an orifice you have, for natural gas or propane. Results are estimates; the rating plate and the maker's conversion kit decide.

What do you want to find?
Gas type

From the rating plate. If the plate already shows a high-altitude input, enter that and leave altitude at 0.

The number or millimeter size stamped on the orifice. Choose "Other diameter" for a measured hole.

Orifices sharing the input. Many fireplace burners use two different sizes; the maker's sizes always win.

Typical: natural gas 3.5, propane 10.0 (some ratings use 11.0). Use your rating plate value.

Above 2,000 ft, US practice reduces input 4% per 1,000 ft above sea level.

Advanced: gas properties

Estimates only. These figures come from the standard orifice equation (discharge coefficient 0.90) and are accurate to roughly plus or minus 5%. Real orifices, burners and gas vary. Your appliance's rating plate and the maker's conversion kit always take priority, and orifice changes or gas conversions must be done by a qualified gas installer.